DRS-5V30W1NZ
Ultra-compact size and galvanic isolation up to 3.0KVac between input to output and input to ground. Universal AC input voltage and full power from -10°C to +55°C operation. Up to 89.0% efficiency. Low earth leakage current < 0.5mA @ 264Vac. Built-in DC OK relay contact option available. Extreme low temperature cold start at -40°C. NEC Class 2 / Limited Power Source (LPS) certified.
main specifications drc-5v30w1nz:
Nominal Input Voltage: 100-240Vac
Input Voltage Range: 85-264Vac
Nominal Input Frequency: 50-60Hz
Input Frequency Range: 47-63Hz
DC Input Voltage Range: 120-375Vdc
Nominal Output Voltage: 5V
Output Voltage Adjustment Range: 5.0-5.5Vdc
Output Current: 3A
Output Power: 15W
Line Regulation: < 0.5% (@ 85-264Vac, 100% load)
Load Regulation: < 1.0% (@ 85-264Vac, 0-100% load)